Transformer  Polylux TIP50A
Transformer  Polylux TIP50A

We are not the manufacturer, authorised distributor or authorised representative of the Polylux brand in South Africa. The private labels and part numbers shown on this website are the property of their respective owners.

Polylux TIP50A

Manufacturer

Polylux

Country

Spain

Part number

TIP50A

Category

Transformers

Type

Transformer

Stock availability:

On request

Price: On request

Order

Several positions are needed?

Send your request on email:

Worldwide delivery services:
fedex dhl ups
Ways of payment:
wire transfer paypal

Specifications TIP50A

Measuring transformers

The short circuit on terminals or the connection to earth can be achieved by the double fast-on or connecting two wires on the same terminal.

Protection transformers

The C.T. when used as a current generator for protection relays has electrical characteristics which differ from those of the measuring transformer.

In fact, the measuring C.T. is expected to give a saturation of the magnetic circuit with 5P in primary currents, while in the case of protective C.T., it is necessary for the secondary current value to follow the increase in the primary current up to 10-15-20In, so as to guarantee the intervention of the relay in the case of unforeseen breakdown current.

It is important not to load the C.T. with a P performance which is greater than that indicated, so as not to modify the saturation value of the C.T.

P=R∗I2

P = Load on the C.T.

R = Resistance of the relay and resistance of the cables

I = Nominal secondary current of the C.T.

Features TIP50A


: 50 A
: 5 A
Class: 3 Rating: 1,5 VA
Frequency: 50 - 60 Hz
Thermic short circuit current: 40 IpN 1 seg.
Dynamic short circuit current: 2,5 I th 1 seg.
Permanent overloading: 120% Icth
Insulation: In air, Class E
Test voltage: 3kv (50Hz) 1 min.
Protection degree: IP30
Ambient temperature: -20ºC a 40ºC
Standards: EN 60044-1
Mounting: Screws and DIN rail
Weight: 0,3 kg
Dimensions (AxBxCxDxE): 58x70x97 mm