Specifications RTOX2.5
Reactor
Anti-flash varnish finish, offering:
- Protection against corrosive environments
- Increase of electrical isolation
- High compression capacity
- Reduction of noise level
- Increase of product's lifespan
Safety class I
Includes thermal protection against overtemperatures
Possibility of tailor-made manufacturing
Technical remarks about the use of line reactors:
- Attenuation of voltage peaks in the output of the converter, protecting against premature degradation of the dielectrical parts of the motor
- Reduction of the reflection effect due to the length of the cables between the converter and the motor. This effect amplifies voltage values in the terminals of the motor
- It is recomended to use these inductances for lengths over 50 m from the converter to the motor
Features RTOX2.5
Rated current: 2,5 A
Motor rating: 0,75 kW / 1 CV
Line voltage: 380 - 460 V
Reactor: 8,821 mH (50 Hz)
Voltage drop: 3% (50 Hz)
Thermal overload factor: 0,05
Frequency: 50/60 Hz
Protection degree: IP-00
Cooling: AN
Ambient temperature: 40ºC
Temperature rise: Class F
Insulation: Class F - 155ºC
Windings: Class HC - 200 ºC
Test voltage: 3 kV (1 min, 50 Hz)
Standards: IEC/EN/UNE-EN 60076-6, CE
Mounting: Screws
Include: Bimetal thermal protection
Weight: 2 kg
Dimensions (AxBxCxDxE): 150x110x184,5x49x100 mm 6Ø