We are not the manufacturer, authorised distributor or authorised representative of the IFM brand in South Africa. The private labels and part numbers shown on this website are the property of their respective owners.
Application | |||||||
---|---|---|---|---|---|---|---|
Application | Flow rate control, Temperature control, Wire break detection | ||||||
Electronic data | |||||||
Operating voltage tolerance [%] | -20…10 | ||||||
Operating voltage [V] | 24 DC | ||||||
Current consumption [mA] | 90 | ||||||
Protection class | III | ||||||
Reverse polarity protection | none | ||||||
Power-on delay time [s] | 10…80, (setting (fixed resistors terminals 22-23)) | ||||||
Number of channels | 1 | ||||||
Outputs | |||||||
Characteristic in case of error | In the event of undervoltage, all relays are de-energized, the LED "Low supply/relay connection is broken" light | ||||||
Electrical version | relay | ||||||
Contact load | 4 A (250 V AC / 30 V DC) | ||||||
Switching relay energized when flow is present and during the power-on delay time | |||||||
Switching function temperature monitoring | relay de-energized in case of wire break or short circuit | ||||||
Relay de-energised in case of wire break or short circuit | >|||||||
Short circuit protection | none | ||||||
Overcurrent protection | none | ||||||
Response time | |||||||
Response time [s] | <3 | ||||||
Software / Programming | |||||||
Switch point setting | with potentiometer | ||||||
Preset selection for liquids/gases | wire bridge, device factory setting: liquid media monitoring, for gaseous media monitoring: connect terminals 23 / 24. | ||||||
Threshold point setting | with potentiometer | ||||||
Temperature temperature range [°C] | 0…80 | ||||||
Repeatability of set switch point [K] | 4 | ||||||
Operating conditions | |||||||
Ambient temperature [°C] | -20…60 | ||||||
Ambient temperature note |
| ||||||
Degree of protection | IP 20 | ||||||
Tests / approvals th> | |||||||
MTTF [years] | 263 | ||||||
Mechanical data | |||||||
Weight [g] | 237.5 | ||||||
Enclosure | Enclosure for DIN rail mounting | ||||||
Dimensions [mm] | 100 x 25 x 103.5 | ||||||
Material | PBT (polybutylene terephthalate) | ||||||
Displays / Controls | |||||||
Display |
| ||||||
Electrical connection th> | |||||||
Required protection | miniature fuse IEC60127-2 sheet 1, ? 5 A, fast response | ||||||
Notes | |||||||
Notes |
| ||||||
Packing value | 1 piece | ||||||
electrical connection | |||||||
Connection | Combicon connector: |