We are not the manufacturer, authorised distributor or authorised representative of the IFM brand in South Africa. The private labels and part numbers shown on this website are the property of their respective owners.
Manufacturer
IFM
Country
Germany
Part number
SA2000
Description
Flow sensor for measurement of flow and temperature at the same time
Stock availability:
On request
Application | |||||||
---|---|---|---|---|---|---|---|
Media | Water, glycol solutions, backlash, oils | ||||||
Medium note |
| ||||||
Measured medium temperature [°C] | -20…90 | ||||||
Pressure strength [bar] | 100 | ||||||
MAWP (for CRN application) [bar] | 85 | ||||||
Electronic data | |||||||
Operating voltage [V] | 18…30 DC | ||||||
Current consumption [mA] | <100 | ||||||
Protection class | III | ||||||
Reverse polarity protection | yes | ||||||
Power-on delay time [s] | 10 | ||||||
Inputs/outputs | |||||||
Number of inputs and outputs | Number of digital outputs: 2 , Number of analog outputs: 1 | ||||||
Outputs | |||||||
Total number of outputs | 2 | ||||||
Output signal | Switching signal, analogue signal, frequency signal, IO-Link, (configurable) | ||||||
Electric Hard version | PNP/NPN | ||||||
Number of digital outputs | 2 | ||||||
Output function | normally open / normally closed, (parameterizable) | ||||||
Max. voltage drop of switching output DC [V] | 2.5 | ||||||
DC load current of switching output DC [mA] | 250 | ||||||
Number of analog outputs | 1 | ||||||
Analog current output [mA] | 4…20, (scalable) | ||||||
Maximum load [?] | 350 | ||||||
Short-circuit protection | yes | ||||||
Short-circuit protection type | clocked | ||||||
Overcurrent protection | yes | ||||||
Output frequency [Hz] | 0…1000 | ||||||
Measuring/setting range | |||||||
Probe length L [mm] | 19.2 | tr>||||||
Operating mode | Relative, Absolute liquid, Absolute gaseous | ||||||
Note on setting range |
| ||||||
Liquid media | |||||||
Measuring range [m/s] | 0.04…3 | ||||||
Parameter setting within [m/s] | 0…6 | ||||||
Gases | |||||||
Measuring range [m/s] | 2…100 | ||||||
Parameter setting within [m/s] | 0 …200 | ||||||
Temperature control | |||||||
Measuring range [°C] | -20 …90 | ||||||
Resolution [°C] | 0.2 | ||||||
Accuracy/Uncertainty th> | |||||||
Flow rate control | |||||||
Temperature drift [cm/s x 1/K] | 0.003 m/s x 1/K ( 70 °C) | ||||||
Max. temperature gradient (rate of change of medium temperature) [K/min] | 100 | ||||||
Accuracy (in measuring range) | ± (7 % MW + 2 % MEW) instructions, Accuracy may differ for different media and mounting positions.) | ||||||
Repeatability | 0.05 m/s, (Water, Flow velocity: 0, 05…3 m/s) | ||||||
Temperature control | |||||||
Temperature drift | ± 0.005 K/°C | ||||||
Accuracy [K] | ± 0.3 / ± 1, (Water, Flow rate: 0.3…3 m /s / backlash, Flow velocity:> 10 m/s) | ||||||
Response time | |||||||
Flow velocity control | |||||||
Response time [s] | 0.5, (T09, Water, glycol: 0.8 s, backlash: 7 s, oil: 1 .8 s, each T09) | ||||||
Temperature control | |||||||
Dynamics of response T05 / T09 [s] | 1.5 (T09), (Water, Flow rate: 0.3…3 m/s) | ||||||
Software / Programming | |||||||
Parameter selection | hysteresis/window, normally open/normally closed, switching logic, current/frequency output, medium selection, damping, learning function, display can be rotated and switched off, standard unit of measure, color of operating value | ||||||
Interfaces | |||||||
Communication interface | IO-Link | ||||||
Transmission method | COM2 (38.4 kBaud) | ||||||
IO- Link verification | 1.1 | ||||||
SDCI standard | IEC 61131-9 | ||||||
IO-Link device ID | 533 d / 00 02 15 h (REL) | ||||||
Profiles | Smart Sensor: Process Data Variable, Device Identification, Device Diagnosis | ||||||
SIO Mode | yes | ||||||
Desired port type td> | A | ||||||
Analog operating data | 2 | ||||||
Binary operating data yes data | 2 | ||||||
Min. cycle time [ms] | 3 | ||||||
Operating conditions | |||||||
Ambient temperature [°C] | -40…80 | ||||||
Storage temperature [°C] | -40…100 | ||||||
Degree of protection | IP 65, IP 67 | ||||||
Tests / approvals | |||||||
EMC |
| ||||||
Impact resistance |
| ||||||
Vibration resistance |
| ||||||
MTTF [years] | 143 | ||||||
UL Certification |
| ||||||
Mechanical data | |||||||
Weight [g] | 323, 8 | ||||||
Material | stainless steel steel (1.4404 / 316L), stainless steel steel (1.4310 / 301), PBT-GF20, PBT-GF30 medium | stainless steel steel (1.4404 / 316L), gasket: FKM | |||||
Process connection | G 1/2 threaded connection | ||||||
Displays / Controls | |||||||
Display |
| ||||||
Notes | |||||||
Notes |
| ||||||
Packing quantity | 1 piece | ||||||
Electrical connection | |||||||
Connection td> | Connector: 1 x M12, Contacts: gold-plated |