PSU-1AC/24VDC-5A IFM DN4012
 PSU-1AC/24VDC-5A IFM DN4012

We are not the manufacturer, authorised distributor or authorised representative of the IFM brand in South Africa. The private labels and part numbers shown on this website are the property of their respective owners.

IFM PSU-1AC/24VDC-5A DN4012

Manufacturer

IFM

Country

Germany

Name

PSU-1AC/24VDC-5A

Part number

DN4012

Description

Switched-mode power supply 24 V DC

Stock availability:

On request

Price: On request

Order

Several positions are needed?

Send your request on email:

Worldwide delivery services:
fedex dhl ups
Ways of payment:
wire transfer paypal

Specifications PSU-1AC/24VDC-5A DN4012

For the regulated power supply for controllers, sensors, actuators, and industrial electronics. Low power loss thanks to high efficiency. High mains buffering time. Particularly space-saving design. High power reserves.

Features PSU-1AC/24VDC-5A DN4012

Electronic data
AC frequency [Hz]47…64
Operating voltage tolerance [%]10
Operating voltage tolerance 2 [%]10
Operating voltage [V]Auto ranging
Rated AC voltage [V ]<230
AC input voltage [V]100…120 / 200…240
Output voltage DC [V]24…28
Protection classI, ( IEC 61140)
Surge protectionYes, (<39 DC)
Output voltage [V]adjustable, output voltage SELV, PELV
Max. output current at min. output voltage [A]5
Max. output current at max. output voltage [A]4.3
Max. output current peak at min. output voltage [A]6
Max. output current peak at max. output voltage [A]5.1
Output power (constant) [W]120
Output power (peak) [W]144
Note on output power (peak)
? 45 °C permanently allowed,> 45 °C <1 minute every 10 minutes
Note on power factor (nominal voltage 120 V AC / 60 Hz)0.56
Note on power factor (nominal voltage 230 V AC / 50 Hz)0.47
Power reserve [%]20
Number - circuits for connecting safety sensors1
Max. residual ripple [mV]50
Peak current at switch-on (nominal voltage 120 V AC / 60 Hz) [A]3
Peak make current (nominal voltage 230 V AC / 50 Hz) [A]3
Starting current limitationyes
Efficiency (nominal voltage 120 V AC / 60 Hz) [%]89.4
Efficiency (nominal voltage 230 V AC / 50 Hz) [%]90.2
Secure external input? B-10 A / ? C-6 A
Derating tolerances [W/K]3 (60…70 °C)
Operating time when power is off (nominal voltage 120 V AC / 60 Hz) [ms]80
Operating time at power failure (nominal voltage 230 V AC / 50 Hz) [ms]78
Input current (nominal voltage 120 V AC / 60 Hz) [A]2.05
Input current (nominal voltage 230 V AC / 50 Hz) [A]1 .23
Power loss (nominal voltage 120 V AC / 60 Hz) [W]14.5
Power loss (nominal voltage 230 V AC / 50 Hz) [W]13.2
Reverse voltage protection [V] 35
Outputs
Short circuit protectionyes
Overcurrent protectionyes
Tolerable overloadpermanent output current
Operating conditions
Ambient temperature [°C]-25…70
Note on ambient temperature td>
keep free space for convection (see operating instructions)
Storage temperature [°C]-40…85
Max. permissible relative humidity [%]95, (IEC 60068-2-30)
Degree of protectionIP 20, (EN 60529)
Pollution degree2, (IEC 62103: no conductive pollution allowed)
Tests / Approvals
EMC
EN 61000-6-1
EN 61000-6-2
EN 61000-6-4
Vibration resistance
IEC 60068-2-6±1.6 mm 2…17.8 Hz / 2 g 17.8…500 Hz
Impact resistance
IEC 60068-2-2730 g 6 ms / 20 g 11 ms
Mechanical data
Weight [g]594.5
Mountingrail, (TH35 (EN 60715))
Dimensions [mm]124 x 40 x 122.5
Material Steel sheet
Displays / Controls
Display
DC-ok1 LED
Notes
Notes
Standard connection of outputs only valid for identical devices up to max. 150 V DC total voltage
100 V AC supply and a constant P> 120 W can lead to thermal shutdown.
Packing quantity1 piece
electrical connection
Connectionscrew terminals:
diagrams and graphs
Chart block
output characteristics
characteristic curve for efficiency level / power loss
characteristic line for tolerances from nominal values
Characteristic straight line for power down operation time